HL Series Process Temperature Control System

Features • Can view historical alarms, temperatures, curves, and export temperature data • Fully closed pipeline design increases energy conversion sales and reduces the risk of heat transfer medium volatilization and moisture absorption. • Directly turn on the compressor to cool down when the temperature is 200℃ • The temperature range is -40℃~200℃ without replacing the thermal conductive medium to achieve contact temperature control • Multifunctional alarm system and safety features with excellent performance, high precision and intelligent temperature control
Category Tag

Water Temperature Control Unit

● Control system: PID control

● Heat transfer medium temperature control accuracy: ±0 . 5c

● Temperature control accuracy of reaction material: ±1c

● Ahell material: cold plate spray

● Communication protocol: MODBUS RTU protocol RS 48

● Medium temperature range: -25c~200c (high temperature can be extended to 250c)

● Operation panel: 7 inch color touch, temperature curve display, record

● Temperature control object: material temperature control and thermal media outlet temperature control can be freely selected

● Temperature difference control: The temperature difference between the reactorjacket temperature and the material temperature can be controlled and set

● Program editing: 5 programs can be programmed, and each program can program 30 steps.

● Temperature feedback: the heat conduction medium of the equipment local temperature, outlet temperature, reactor material temperature (external temperature sensor) three point temperature PT100

● Safety protection: with self-diagnosis function, refrigerator overload protection, high pressure pressure switch, overload relay, thermal protection device, low level protection, high temperature protection, sensor fault protection and other safety guarantee functions.

● Closed circulation system: The entire system is a closed system. There will be no oil mist at high temperatures and no moisture in the air absorbed at low temperatures. The system will not increase pressure due to high temperatures during operation. The heat transfer medium will be automatically replenished at low temperatures.

-25200HL Series Process Temperature Control System

HL Series Process Temperature Control System

-60200

-80-200HL Series Process Temperature Control System

Technical Parameters

Model HL25-220 HL35-220 HL55-220 HL75-220 HL100-220
Heating power 2.5kW 3.5kW 5.5kW 7.5kW 10kW
Cooling capacity 200℃ 2.5kW 3.5kW 5.5kW 7.5kW 10kW
100℃ 2.5kW 3.5kW 5.5kW 7.5kW 10kW
20℃ 2.5kW 3.5kW 5.5kW 7.5kW 10kW
-5℃ 2kW 3kW 4.5kW 6.6kW 8kW
-20℃ 1.0kW 1.8kW 2.8kW 3.8kW 4.6kW
Circulating pump Flow Max30L/min Max30L/min Max42L/min Max56L/min Max56L/min
Pressure 1.5bar 1.5 bar 2.0 bar 2.0 bar 2.0 bar
Compressor SECOP EMERSON COPELAND
Expansion valve DANFOSS
Thermal medium interface size DN15 DN20 DN20DN20 DN25
20c cooling water demand 0.6m³/h 0.8m³/h 1m³/h 1.2m³/h 1.6m³/h
1 . 5bar~4bar 1 . 5bar~4bar 1 . 5bar~4bar 1 . 5bar~4bar 1 . 5bar~4bar
Cooling water interface size G1/2 G1/2 G3/4 G3/4 G3/4
Dimension mm Water-cooling 400*600*1150 400*600*1150 500*680*1250 550*700*1600 500*680*1250
Air-cooled 400*600*1250 450*650*1300 550*750*1400 570*750*1500 650*700*1650
Weight Water-cooling 100kg 135kg 160kg 205kg 250kg
Air-cooled 115kg 165kg 285k 230k 280kg
Power supply/Voltage AC 220V 50HZ AC 380V 50HZ AC 380V 50HZ AC 380V 50HZ AC 380 V50HZ
Total power 4kW(max) 6kW(max) 8kW(max) 11kW(max) 14kw(max)

 

Model HL150-220 HL250W-220 HL380W-220 HL600W-220 HL950W-220
Heating power 15kW 25kW 38kW 60kW 95kW
Cooling capacity 200℃ 15kW 25kW 38kW 60kW 95kW
100℃ 15kW 25kW 38kW 60kW 95kW
20℃ 15kW 25kW 38kW 60kW 95kW
-5℃ 12kW 19kW 30kW 46kW 70kW
-20℃ 7kW 12kW 16kW 22kW 32kW
Circulating pump Flow Max110L/min Max120L/min Max150L/min Max300L/min Max400L/min
Pressure 2.5bar 2.5bar 2.5bar 2.5bar 2.5bar
Compressor EMERSON COPELAND DORIN/BITZER/FRASCOLD
Expansion valve DANFOSS EMERSON COPELAND/DANFOSS
Thermal medium interface size DN32 DN32 DN40 DN40 DN50
20c cooling water demand 2m³/h 6m³/h 10m³/h 14m³/h 20m³/h
1 . 5bar~4bar 1 . 5bar~4bar 1 . 5bar~4bar 1 . 5bar~4bar 1 . 5bar~4bar
Cooling water interface size G1 DN32 DN40 DN50 DN65
Dimension mm Water-cooling 700*800*1650 1000*950*1650 1000*950*1750 2000*1250*1750 2000*1250*1750
Air-cooled 750*750*1800 / / / /
Weight Water-cooling 280kg 480kg 750kg 1000k 1250kg
Air-cooled 300kg / / / /
Power supply/Voltage AC 380V 50HZ AC 380V 50HZ AC 380V 50HZ A C380V 50HZ AC 380V 50HZ
Total power 21kW(max) 34kW(max) 51 kW(max) 78kW(max) 120kW(max)

 

● Optional: SUS 304 shell, ExdII BT4 explosion-proof, ExdII CT4 explosion-proof, positive pressure explosion-proof (positive pressure explosion-proof can only use water cooling)